Daily safety and water-chemistry verification for industrial steam and hot-water boilers covering low-water cutoffs, relief valves, and burner flame stability.
Compare the primary analog pressure gauge against the BMS/PLC digital transmitter; investigate any discrepancy greater than 3% and confirm pressure is safely below MAWP.
Open the water column drain valve for 3–5 seconds, close it, and observe water returning briskly to the normal operating level (NWOL) in the gauge glass to confirm no sludge blockage.
Perform a slow-drain evaporation or float-chamber test on the primary LWCO and verify the burner trips immediately at the low-water setpoint and requires manual reset if applicable.
Observe flame color and stability through the sight port (clean blue/orange depending on fuel), verify gas/oil supply pressures, and check stack temperature for soot fouling.
Execute scheduled bottom blowdown to purge dissolved solids, test feedwater hardness/pH/sulfite levels, and record all readings in the boiler logbook.
ASME and most jurisdictional boiler codes require daily blowdown testing of float-type LWCOs while the boiler is under pressure, plus a slow-drain evaporation test at least monthly or per manufacturer schedule.
A slow-returning water level indicates scale, mud, or sediment partially blocking the lower water-column piping or try-cock connections, which creates a false high-water reading and dry-fire risk.