Weekly fire-prevention and sanitation SOP for commercial kitchen Type I exhaust hoods, baffle filters, and grease interceptors. Reduces grease fire risk and drain backups.
Turn off all fryers, ranges, and charbroilers, allow surfaces to cool, and switch off the hood exhaust fan before removing filters.
Remove stainless steel baffle filters, soak in heavy-duty alkaline degreaser, run through high-temp warewasher, and air dry completely.
Empty and wash grease drip cups, wipe down accessible hood plenum surfaces, and visually confirm fire suppression nozzles and fusible links are grease-free.
Open the grease interceptor lid, measure FOG (fats, oils, grease) thickness, skim floating grease into a sealed waste drum, and verify outlet baffle flow.
Reinstall dry baffle filters with zero gaps (so flames cannot enter the plenum), restart exhaust and make-up air fans, and verify proper draw.
In high-volume kitchens using fryers, woks, or charbroilers, baffle filters should be cleaned daily or at least weekly. NFPA 96 also requires periodic professional hood and ductwork cleaning based on cooking volume.
Follow the 25% rule: once combined floating grease and settled solids reach 25% of the trap's liquid depth, it must be pumped to prevent sewer backups and municipal fines.