Monitor ISO-classified cleanroom positive/negative differential pressures (Magnehelic gauges), temperature, and relative humidity per shift to prevent cross-contamination.
Check the BMS or hallway display to confirm supply and exhaust AHUs are running normally with no active HEPA filter differential pressure alarms.
Read each airlock and suite Magnehelic gauge at eye level; confirm Grade B/C/D cascades maintain ≥10–15 Pa positive pressure (or negative for potent APIs).
Record calibrated digital thermo-hygrometer values against suite limits (typically 18–25°C and 30–60% RH) before starting aseptic or dispensing work.
Verify both airlock doors cannot open simultaneously; if pressure drops below alert limit, halt operations and notify QA and Engineering immediately.
EU GMP Annex 1 and ISO 14644-4 recommend a minimum differential pressure of 10 to 15 Pascals (Pa) between adjacent rooms of different cleanliness grades.
Operations must be paused immediately, affected open product quarantined, and QA must investigate potential microbial or particulate ingress before resuming.
Verify chemical fume hood face velocity (80–120 fpm), sash working height stop, and baffle airflow before handling volatile or toxic reagents.
Perform daily level-bubble check, internal/external weight verification with Class E2/F1 NIST weights, and sensitivity check on analytical balances.
Flush plumbed emergency eyewash stations and drench showers weekly to clear stagnant sediment, verify tepid water flow, and keep access paths clear.