Monthly statutory inspection SOP and QR checklist for portable ABC, CO2, and foam fire extinguishers across commercial buildings.
Confirm the extinguisher is mounted in its designated location, unobstructed by storage, and has clear signage visible from the corridor.
Check that the pressure gauge needle sits squarely in the green operable zone (for stored-pressure units) and inspect the shell for dents, rust, or leakage.
Verify the plastic tamper seal is intact and the safety pull pin is properly seated without bending or corrosion.
Inspect the discharge hose and horn for cracks or blockages; for CO2 units, verify gross weight against the stamped tare weight.
Record the inspection date and technician initials on the physical tag or scan the asset QR code to submit the digital statutory log.
NFPA 10 requires a visual quick-check at least once every 30 days (monthly), alongside an annual maintenance examination by a certified technician.
Tag the unit out of service immediately, replace it with a charged spare of equal or higher rating, and send the unit for professional recharging.
Digital QR logs provide timestamped audit trails for ISO 41001 and insurers, though many local fire marshals still require a physical tag attached to the neck.