Weekly health and thermal inspection for VRLA/flooded industrial battery banks and online double-conversion UPS systems.
Record input/output voltage, load percentage per phase, DC bus float voltage, and verify the UPS is in Online Normal mode (not Static Bypass).
Visually inspect VRLA/flooded cells for case bulging, cracks, electrolyte weeping, or white/green sulfation on inter-cell busbars.
Verify battery room cooling maintains 20–25°C (68–77°F) and use an IR thermometer to spot warm terminals indicating loose torque.
Confirm hydrogen exhaust fans are running (especially for flooded/NiCd banks) and acid-neutralizing spill kits and eyewash stations are ready.
Every 10°C (18°F) rise above the 25°C design baseline cuts VRLA battery service life roughly in half due to accelerated grid corrosion.
Bulging indicates internal overpressure from thermal runaway or excessive overcharging; isolate and replace the affected block immediately.
Weekly performance, thermal, and DC string health inspection for commercial/utility-scale solar PV inverters and combiner boxes.
Daily external inspection SOP for oil-immersed distribution and power transformers covering MOG oil level, OTI/WTI temperatures, and silica gel breather.
Daily perimeter, switchyard, and control-room safety walkthrough for industrial and utility electrical substations.