Weekly performance, thermal, and DC string health inspection for commercial/utility-scale solar PV inverters and combiner boxes.
Check the inverter display or SCADA portal for grid-tie status, isolation resistance (Riso) faults, and compare DC string currents for >10% imbalance.
Check DC surge protection device (SPD) status windows (green = OK, red = replace) and scan string fuse holders with an IR thermometer for hot spots.
Verify cooling fans spin freely without bearing rattle and clear dust or insect debris from intake louvers and heatsink fins to prevent thermal derating.
Inspect combiner door gaskets for moisture ingress, confirm MC4/cable glands are tight, and verify equipment grounding jumpers are intact.
Common causes include a blown string fuse, a corroded or loose MC4 connector, localized module shading, or a bypassed diode inside a panel.
A sacrificial SPD module that tripped during a lightning surge leaves the inverter unprotected against the next transient unless replaced promptly.
Daily external inspection SOP for oil-immersed distribution and power transformers covering MOG oil level, OTI/WTI temperatures, and silica gel breather.
Daily perimeter, switchyard, and control-room safety walkthrough for industrial and utility electrical substations.
Weekly health and thermal inspection for VRLA/flooded industrial battery banks and online double-conversion UPS systems.