Daily external inspection SOP for oil-immersed distribution and power transformers covering MOG oil level, OTI/WTI temperatures, and silica gel breather.
Log the Oil Temperature Indicator (OTI) and Winding Temperature Indicator (WTI) readings along with max-drag needle positions and ambient temperature.
Check the Magnetic Oil Gauge (MOG) on the conservator tank against the ambient temperature reference mark to ensure no slow oil leak.
Confirm breather silica gel is vibrant blue/orange (not pink/clear) and oil is visible in the bottom cup; inspect Buchholz sight glass for trapped gas.
Verify radiator cooling fans activate at setpoints, inspect HV/LV porcelain bushings for cracks or tracking, and check radiator valves and gaskets for oil weeping.
It indicates the desiccant is saturated with moisture and can no longer dry incoming air, risking moisture ingress into the insulating oil.
Gas accumulation signals an internal incipient fault (arcing or overheating); schedule an immediate Dissolved Gas Analysis (DGA) oil sample.