Monthly non-invasive inspection of 11kV/33kV medium-voltage switchgear rooms covering partial discharge, heaters, VCBs, and interlocks.
Verify switchgear room relative humidity is below 60% and check panel anti-condensation space heaters are drawing normal current.
Scan cable termination compartments and busbar chambers externally with an ultrasonic/TEV detector for early corona or tracking noise.
Verify vacuum circuit breaker (VCB) spring-charged indicators, operation counters, trip-coil healthy LEDs, and protection relay status.
Confirm mechanical interlocks and padlocks on earthing switches, and verify insulated rubber mat (IEC 61111) integrity in front of the lineup.
Moisture condensing on 11kV/33kV epoxy insulators creates conductive tracking paths that can trigger catastrophic phase-to-ground flashovers.
It means the breaker's trip coil, DC fuse, or auxiliary contact path is open—so the breaker will fail to trip automatically during a short-circuit.
Weekly performance, thermal, and DC string health inspection for commercial/utility-scale solar PV inverters and combiner boxes.
Daily external inspection SOP for oil-immersed distribution and power transformers covering MOG oil level, OTI/WTI temperatures, and silica gel breather.
Daily perimeter, switchyard, and control-room safety walkthrough for industrial and utility electrical substations.